Digital Input |
NEIO-B1101 Type: PNP Input Voltage: 24 VDC On-State Voltag, “1“: - 15~30 VDC (IEC 61131-2 type 1) - 11~30 VDC (IEC 61131-2 type 2/3) Off-State Voltag, “0“: 0~5 VDC (IEC 61131-2 type 1/2/3) Inpurt Filter: 3 ms NEIO-B1102 Type: PNP/NPN Input Voltage: 24 VDC On-State Voltag, “1“: 9~24 VDC/0~15 VDC Off-State Voltag, “0“: 0~8 VDC/16~24 VDC Inpurt Filter: 1 ms |
Communication | Protocol: EtherCAT Bus interface: 2 x RJ-45 (daisy-chain) Media: Ethernet cable (min. CAT 5), shielded Distance between stations: maximum. 100m (100BASE-TX) Data transfer rate: 100M baud |
Power Requirements |
DC input range: DC 24V ±20% with over-voltage and reversed-voltage protection
NEIO-B1101 Power Consumption: 2 W NEIO-B1102 Power Consumption: 2.5 W |
Common Section | Electrical isolation: 2.5 kV (power contact) Operating temperature: 0°C to 55°C Storage temperature: -40°C to 85°C Relative humidity: 5~95%, non-condensation, non-operating Shock: IEC 60068-2-27 Vibration: IEC 60068-2-6, IEC 60068-2-64 Enclosure type rating: IP20 Mounting type: din-rail (35mm), wall-mount Dimesions (mm): 155 (W) x 115 (H) x 57.4 (D) |
Certifications | CE FCC Class A |